Lightning and surge arrester for installation in the DC circuits of solar photovoltaic systems

Protector Type 2 (Class C), indicated for the protection of current circuits in photovoltaic panels.
Maximum discharge current up to 40 kA (8/20).
Maximum continuous operating voltage for PV application: Ucpv > 1,2 X UOC STC

Characteristics
  • V/Y connection.
  • Zinc oxide varistors
  • Easily replaceable plug-in modules with locking system.
  • Base and modules configured for secure mounting.
  • Easy maintenance through local fault locator.
Download data sheet
PDF icon SLS-PV700 V/Y
  • IEC 61.643-11:2011
  • EN 61.643-11:2012
  • UNE 61.643-11:2013
  • IEC 62.305-1, 2, 3 y 4
  • UNE 21.186:2011
  • NFC 17-102:2011
  • UNE EN 60.664-1:2008 ·
  • RBT
Scheme
Technical specifications
Description Ref. Nb. Phases Grade
protec.
Range Tª work A (mm) B (mm) C (mm) D (mm) E (mm) Weight (g)
SLS-PV700 V/Y 370239 3F IP20 de -40º a 80ºC 54 82 72 45 44 340
protective parameters    
Maximun operating voltage UCPV 750 V DC
Nominal discharge current (8/20 μs) In 20 kA
Maximum discharge current (8/20 μs) Imax 40 kA
Voltage protection level Up 3,6 kV
Response time ta 25 ns
Cross-section of connected conductors solid ISO:1/35 mm2 ; AWG:17/2
Cross-section of connected conductors stranded ISO:1/25mm2 ; AWG:17/4
Fault indication Si
Mounting DIN rail