Conductors, fastening and connection components that form the down conductor system to ground.

REQUEST MORE INFORMATION

ESE down conductors

conductores de bajada para PDC

The lightning rod is connected to ground with at least two down conductors located on opposite facades whenever possible.

The down conductors must be installed outside the building, avoiding the proximity of electrical cables and gas.

Its path must be as straight as possible, using the shortest path to earth, avoiding any sharp bend or lift.

When several ESEs are installed on the same building they can share down conductors.

The down conductor to ground must be properly fixed and tensioned, using as a reference three clamps per meter of conductor. Protect the lower part of the down conductor with a protective tube of at least 2 meters. It is recommended to install a lightning counter above the protective tube to enable verification and maintenance of the installation.

 

 

LPS passive down conductors

In order to reduce the likelihood of damage due to lightning currents circulating in the LPS, down conductors must be arranged so that from the point of impact grounding is:

Protection LevelDistance between conductors
I10 m
II10 m
III15 m
IV20 m

 

esquema conductor de bajada sistema de proteccion contra el rayo

It is also advisable to place the down conductors on exposed corners of the building whenever constructively possible.

The dimensions and materials of the ground down conductors, must meet the requirements contained in IEC 62561-2.

The conductors that form the mesh must be properly set, taking as reference 1 conductor clamp per meter.

Protect the bottom of the downspout with a protective tube of at least 2 m.

Install section elements in each of the down conductors to allow for measurement of the ground.

LPS passive scheme:

A: Horizontal conductor cover

B: Grounded conductor

C: Down conductor isolator